• 1800 648 070
  • This email address is being protected from spambots. You need JavaScript enabled to view it.

10KV Composite Insulator

Transmission - Insulators - Polymer Strain Insulators - 10KV Composite Insulator
Part No. Fig. Rated Voltage
(kV)
Specified Mechanical Load
(kN)
Socket & Ball Size Section Height H
(mm)
Minimum Arcing Distance H
(mm)
Shed Diameter D
(mm)
Min Nominal Creepage Distance L
(mm)
Lighting Impulse Withstand Voltage Wet Power Freq. Voltage Weight (kg)
1.1-1000-10/70-WT 1 10 70 16 319ยฑ5 159 92 415 95 60 1.6
1.1-1000-10/70-DT 2 10 70 16 312ยฑ5 159 92 415 95 60 1.1
1.1-1000-10/70-UD-1 3 10 70 / 342ยฑ5 155 150 400 95 60 1.6
1.1-1000-10/70-WD 4 10 70 16 322ยฑ5 159 92 415 95 60 1.6
1.1-1000-10/70-UD-2 5 10 70 / 318ยฑ5 159 92 415 95 60 1.5
1.1-1000-10/3 6 10 3 (Curve) / 200ยฑ5 130 140  380 95 40 1.6