• 1800 648 070
  • This email address is being protected from spambots. You need JavaScript enabled to view it.

330KV AC Composite Insulator

Transmission - Insulators - Polymer Strain Insulators - 330KV AC Composite Insulator
Part No. Rated Voltage
(kV)
Specified Mechanical Load
(kN)
Socket & Ball Size Section Height H
(mm)
Minimum Arcing Distance H
(mm)
Large/Small Shed Diameter D/d
(mm)
Shed Spacing B
(mm)
Diameter of Corona Ring D1, D2
(mm)
Min Nominal Creepage Distance L
(mm)
Lighting Impulse Withstand Voltage Wet Switch Impulse Withstand Voltage Wet Power Freq. Voltage Weight (kg)
1.1-1000-3-330/100 330 100 16 2930ยฑ40 2600 171/85 79 400 9075 1425 950 570 15
1.1-1000-4-330/100 330 100 16 2990ยฑ40 2600 171/85 79 400 9075 1425 950 570 15
1.1-1000-3-330/160 330 160 20 2930ยฑ40 2600 171/85 79 400 9075 1425 950 570 18
1.1-1000-4-330/160 330 160 20 2990ยฑ40 2600 171/85 79 400 9075 1425 950 570 18
1.1-1000-3-330/210 330 210 20 2930ยฑ40 2600 171/85 79 400 9075 1425 950 570 18
1.1-1000-4-330/210 330 210 20 2990ยฑ40 2600 171/85 79 400 9075 1425 950 570 18